27 Nisan 2008 Pazar

Quick Selection Coolroom and Freezer Tables

Coolroom Design Data

2°C Coolrooms

External Dimensions : m Heat Load- Watts
Product Load Per Day (Product Entering at 12°C)
Height = 2.4 150 kg 350 kg 700 kg
Length
Width
Average Usage
Heavy Usage
Average Usage
Heavy Usage
Average Usage
Heavy Usage
1.8
1.2
930
1280
1070
1420


1.8
1.8
1120
1560
1260
1690


1.8
2.4
1300
1800
1440
2010


1.8
3
1470
2100
1610
2240


2.4
2.4
1510
2150
1650
2290
1890
2530
2.4
3
1710
2420
1840
2550
2080
2800
2.4
3.6
1900
2660
2030
2800
2270
3040
2.4
4.2


2220
3040
2460
3280
3
3


2060
2850
2310
3090
3
3.6


2280
3130
2520
3370
3
4.2


2490
3390
2730
3630
.6
3.6


2520
3440
2760
3680
3.6
4.2


2750
3730
3060
4040
4.2
4.2


3070
4120
3310
4370

Based on:

  1. 35°C Ambient Temperature
  2. 75mm Polystyrene Insulation
  3. Product Pull Down Time: 24 hours
  4. 16 hours/day compressor operation
  5. Heavy Usage = Average Air Changes x 2

-18°C Freezers

External Dimensions : m
Storage Only- No Product Freezing
Heat Load- Watts
Height = 2.4
Product Load Per Day (Product Entering at 12°C)
Length
Width
150 kg
350 kg
700 kg
1.8
1.2
740
1480
2550

1.8
1.8
930
1660
2730

1.8
2.4
1100
1820
2900

1.8
3
1250
2040
3050

2.4
2.4
1300
2080
3090
4910
2.4
3
1490
2260
3260
5090
2.4
3.6
1670
2430
3430
5260
2.4
4.2
1840
2590
360
5420
3
3
1710
2460
3470
5290
3
3.6
1910
2650
3660
5480
3
4.2
2170
2840
3840
5670
3.6
3.6
2200
2870
3870
5700
3.6
4.2
2420
3080
4150
5910
4.2
4.2
2650
3310
4380
6140

  1. 35°C Ambient Temperature
  2. 150mm Polystyrene insulation
  3. Product pull down time: 24 hours
  4. 18 hours/day compressor operation

The above information should only be used as a guide. It is strongly recommended that a detailed heatload and selection be carried out by BOC staff before equipment is ordered and installed.

Hiç yorum yok: